Aeroo Shield AS06 aerosol fire extinguishing system
Aeroo Shield AS06 aerosol fire extinguishing system

1.049,00 lei + VAT

Aeroo Shield AS06 aerosol fire extinguishing system

1.049,00 lei + VAT

SMOKE / AEROSOL GENERATOR
Protect your property with Aeroo Shield AS06 aerosol fire extinguishing system, advanced technology for maximum safety and fast efficiency. AEROO SHIELD 6 - AS06 is a self-contained and automatic thermal driven aerosol fire extinguishing aerosol generator, specially designed and developed by our company for small spaces.

Checkout SIgur
MAIN FEATURES
  • Instant activation
  • Installation in 5 seconds
  • Leaves no extinguishing residue
  • Unpressurised product
  • Maintenance free
  • No wiring, no batteries

Aerosol fire extinguishing system

AEROO SHIELD 6 - AS06 is a aerosol extinguishing system thermally actuated, self-contained, automatic fire extinguishing system with compact size and light weight, which facilitates installation and fire extinguishing needs in small spaces.

It can be glued to any surface, thanks to the high-strength adhesive strip it comes equipped with. Easy to install.

It is activated by a linear ignition wick, which is initiated when the space temperature reaches 180 ± 20 ºC or on contact with the flame.

The extinguishing agent will rapidly flood the protected space to suppress the fire. The effective protected space of the AEROO SHIELD 6 - AS06 is 0.6 cubic meters.

The product is suitable for small, fire-prone spaces such as electrical panels, control panels, meter boxes, electrical distribution panels (cabinets).

Product data:

  • Product name: AEROO SHIELD 6 - AS06
  • Item number: AS06
  • Discharge time: ≤5 seconds
  • Agent mass: 27 gr
  • Extinguishing capacity: 0.6 mc
  • Working temperature: -30~70 ºC
  • Initiation: at a temperature of 180 ± 20 ºC or in contact with the flame
  • Lifetime: 5 years
  • Size:
    • Base diameter: 85 mm
    • Height: 30 mm

The protection volume of a single unit is 0.6mc, the product shall be placed on top of the protected space, above the point of initiation of a possible fire, with the activation points facing downwards or on the wall of the protected space with the activation points facing the equipment in the protected space. For spaces larger than 0.6mc the technical specification for installation in such spaces should be consulted.

Aeroo Shield AS06 aerosol fire extinguishing system (aerosol fire extinguishing aerosol generator), must be in a closed state prior to spraying to ensure reliable performance. Ensure that there is no obstruction within 100 mm directly in front of the activation diodes of the device and it is not suitable to be installed in the air exhaust position below the protective space. In case of activation, the device will start automatically and can only be touched after it has cooled down.
After activation, ventilate the space by opening the window or door. If not activated before the expiry date, remove and return the device to the supplier.

The product should be stored in a cool dry place with good ventilation and exposure to sunlight should be avoided.

  • It is strictly forbidden to store this product near a heat source
  • It is forbidden to apply pressure to the product
  • It is forbidden to use it after the expiry date